The short answer: a heating cable is rated in watts per metre, but your floor is heated in watts per square metre, and the laying spacing is the bridge between the two. Choose the cable output and the spacing together, not separately, and the same 20 W/m cable can give you 100 W/m² or 200 W/m² depending on how close the runs sit. This guide sets out the exact relationship, shows which output band suits which job, and explains why a cable cannot be cut to length the way a loose film can. Every cable figure comes from the builds on the SunAURA heating cable product page.
Two units that buyers confuse
Linear output, measured in watts per metre (W/m), is the heat each metre of cable gives off. Area output, measured in watts per square metre (W/m²), is the heat spread across the floor. A datasheet talks about the first because the cable is a long, thin element; a heat-loss calculation talks about the second because the room loses heat through its floor area. They are linked by the spacing between adjacent cable runs.
The relationship is simple: area output equals linear output divided by the spacing in metres. A 20 W/m cable laid at 100 mm spacing, which is 0.10 m, gives 20 divided by 0.10, or 200 W/m². The same cable laid at 200 mm spacing gives 20 divided by 0.20, or 100 W/m². The cable has not changed. Moving the runs apart spreads the same heat over more floor and lowers the density; moving them together concentrates it.
This is the single most important idea in cable selection. The W/m rating alone does not tell you the floor output. You need the spacing as well, and the two numbers have to be chosen as a pair to hit the W/m² the room actually needs.

Start from the heat loss, not the cable catalogue
The correct sequence works backwards from the room. First establish the area output the floor needs to offset the room’s heat loss, then pick a cable output and spacing that deliver it. Choosing a cable first and working out the floor later is how projects end up under-powered or overheated.
For a typical insulated indoor room, floor heating is designed around a manageable area output; the product page’s heating systems sit in the same general range as the mat and film builds, with denser outputs reserved for high-loss rooms, wet areas and retrofit situations where the floor is the only heat source. Outdoor and pipe-protection duties use a different logic and are covered below. Once the target W/m² is set, the cable and spacing are constrained by two hard limits: the cable cannot be stretched beyond its fixed length, and it cannot be bent tighter than its minimum radius or laid closer than its minimum spacing.
The output-to-spacing table, with real figures
The table applies the area-output formula to the 10–30 W/m output range on the product page across common spacings. These are engineering figures from the division, not separate product ratings.
| Cable output | At 100 mm | At 150 mm | At 200 mm | At 250 mm |
|---|---|---|---|---|
| 10 W/m | 100 W/m² | 67 W/m² | 50 W/m² | 40 W/m² |
| 15 W/m | 150 W/m² | 100 W/m² | 75 W/m² | 60 W/m² |
| 20 W/m | 200 W/m² | 133 W/m² | 100 W/m² | 80 W/m² |
| 25 W/m | 250 W/m² | 167 W/m² | 125 W/m² | 100 W/m² |
| 30 W/m | 300 W/m² | 200 W/m² | 150 W/m² | 120 W/m² |
Read across any row and the spacing effect is clear. Read down a column and the cable-output effect is equally clear. To hit a target of about 150 W/m², for example, you could use a 15 W/m cable at 100 mm, a 20 W/m cable at roughly 135 mm, or a 30 W/m cable at 200 mm. Several pairs reach the same density, which gives room to match a cable length that fits the area. The underfloor cable spacing guide covers how to keep that spacing even on site.

Why the cable length is fixed and how to match it to the area
A constant-wattage heating cable is supplied as a finished circuit with a set resistance and a fixed heating length. It cannot be shortened to fit a room, because cutting it breaks the resistive circuit and changes the output the thermostat expects. The product page describes a double-conductor build with a single cold tail, so there is no return cable to route back; the whole heating length has to be laid out within the area.
Matching cable to area is therefore a planning exercise. The cable length divided by the area gives the average spacing needed: spacing in metres equals cable length divided by floor area. If a 100 m cable covers a 10 m² floor, the average spacing is 100 divided by 10, or 0.10 m. The supplier sizes the cable kit so that, laid at the recommended spacing, its length covers the usable area and delivers the target density. The practical rule is to measure the actual usable area, excluding fixed cabinets and fixtures, and select the cable length that covers it at the spacing which produces the wanted W/m².
Where the cable is slightly longer than the ideal, the extra length is absorbed by tightening the spacing a little, never by crossing or touching runs. Where it is short, the correct answer is a larger cable, not stretched spacing that leaves cold edges. The comparison in the cable versus mat guide explains why a pre-spaced mat is often easier for a simple rectangular room.
A worked example from room to cable
Running the numbers on a real kitchen shows how the pieces fit. Suppose the usable heated area, excluding the cabinet run and the fridge base, is 8.5 m², and the heat-loss calculation calls for 160 W/m² because the floor is the primary heat source in a moderately insulated room. The total load is 8.5 times 160, or 1,360 W.
Now choose a cable and spacing pair that delivers 160 W/m². From the table, a 20 W/m cable needs spacing of 20 divided by 160, which is 0.125 m, or 125 mm. A 25 W/m cable could instead use spacing of about 156 mm. Taking the 20 W/m option, the required cable length is area times spacing, 8.5 times 0.125, which is about 10.6 m of cable per square metre logic, or more directly length equals area divided by spacing: 8.5 divided by 0.125 gives 68 m of heating cable. The supplier’s nearest standard kit that covers roughly 68 m at 125 mm spacing is selected, with any small surplus absorbed by a slight, even tightening rather than a loop.
At 230 V the 1,360 W load draws about 5.9 A, comfortably inside a 10 A circuit and a 16 A thermostat. At 110 V the same load draws around 12.4 A, which still fits a 16 A breaker but leaves less margin. The point of the example is that the density, the spacing, the length and the current are all derived, not chosen from preference. Once the area and target density are known, the rest follows, and the same steps apply to any room.
What each output band is actually for
The 10–30 W/m range is not a quality ladder where more is better. Each band has a job, and using the wrong one creates either a cold floor or local overheating.
- 10–15 W/m. Suits low-density comfort floors, well-insulated rooms and pipe frost protection where the cable runs along a pipe and only has to hold a modest temperature. Laid close, 15 W/m still reaches a useful indoor density, but the low output keeps surface temperatures gentle.
- 20 W/m. The general-purpose indoor choice. Across normal spacings it spans the comfort-to-retrofit density range, which is why it is the workhorse for underfloor heating in living rooms and kitchens.
- 25 W/m. For higher-loss rooms, bathrooms and situations where the floor is the primary heat source, where a denser output is needed without tightening the spacing to its limit.
- 30 W/m. The top of the range, aimed at outdoor snow and ice melting, roof and gutter protection, and heavy-duty tank or ramp heating where high area outputs are required. Using this indoors at close spacing would overheat the floor and is not appropriate.
The PTC self-limiting option noted on the product page changes the behaviour rather than the nominal band: its output falls as the cable warms, which resists local overheating in coverage-risk and pipe-protection settings. The fixed-output alloy cable gives a steadier, predictable W/m where the design is controlled by a thermostat.

PTC self-limiting versus constant-wattage: a direct comparison
The product page offers both a fixed alloy-resistance cable and an optional PTC, or positive temperature coefficient, build. They solve the same heating problem in different ways and the choice should be made from the installation rather than from a price list.
| Dimension | Constant-wattage alloy cable | PTC self-limiting cable |
|---|---|---|
| Output behaviour | Holds a steady W/m regardless of temperature | Output drops as the cable warms and rises when cold |
| Control | Needs a thermostat to limit temperature | Self-limits at its ceiling, still better with control |
| Overlap risk | Cables must not touch or cross; overlap overheats | More tolerant where coverage is tight, but not cut-proof |
| Best duty | Indoor floors needing predictable even density | Pipe protection, freeze prevention, awkward coverage |
| Limitations | Relies entirely on the control system | Output varies with temperature; cold-start current is higher |
For an indoor floor where the design is built around a fixed target density and a thermostat, the constant-wattage cable is the more predictable tool because its W/m is stable. For pipe frost protection, where the cable sits under insulation and may encounter uneven coverage, the PTC build’s ability to reduce its own output as it warms is a useful guard against overheating. Buyers should not treat PTC as a reason to ignore spacing or control; it is a safety margin in the element, not a replacement for the design. The cold-start inrush of a PTC cable also has to be allowed for when the breaker is sized, since it draws more when first energised at low temperature.
Spacing, surface temperature and hot spots
The area output is an average, but the floor does not heat uniformly at the millimetre scale. Directly above a cable the surface is warmer than in the gap between two runs. If the spacing is too wide, the floor shows warm stripes over the cables and cool bands in the middle, and the thermostat may switch off on the warm reading before the gaps are comfortable.
Keeping the spacing within the recommended range holds the temperature difference between the strip above the cable and the centre of the gap small enough that the floor feels even. Tight, even spacing is particularly important under hard finishes such as tile and stone, which conduct the heat and make any unevenness easier to feel. A floor sensor placed in the gap, rather than directly over a cable, reads the representative surface temperature and prevents early cycling.
Two spacing faults cause most hot-spot problems. Runs that drift closer together in a corner concentrate output in one patch, and cables that touch or cross create a genuine overheating point. The minimum bend radius also matters at turns; a cable forced into a tight kink can be damaged locally. A fixing rail or spaced clips, set before the screed, hold the runs parallel and remove the guesswork. The heating cable installation guide details the fixing methods.
Screed depth, response time and spacing
The cable is almost always embedded in a screed or a layer of tile adhesive, and the depth of that layer interacts with the spacing. A thicker screed stores more heat and evens out the temperature between runs, which tolerates slightly wider spacing, but it also heats up and cools down slowly. A thin bed or a low-profile retrofit build responds quickly but gives less thermal mass to smooth the gap between cables, so spacing has to be tighter and more even.
This affects how the system is run as much as how it is sized. A deep, high-mass screed is best operated on a scheduled setback, warming slowly ahead of occupancy rather than reacting on demand, because rapid response is not available. A thin floor can follow a thermostat more closely. The spacing should be chosen with the build-up in mind: do not use wide spacing in a thin bed and expect the screed to smooth it, because there is not enough mass there to do so. Confirming the planned screed depth and floor finish before fixing the cable prevents a floor that either responds too slowly or shows its cable pattern.
Scene-by-scene output and spacing
Well-insulated living room, supplementary heat. A 15–20 W/m cable at 150–200 mm spacing gives a comfortable average density with an even surface. The wider spacing is fine because the heat load is modest and the floor is not the only source.
Bathroom or kitchen, primary heat. Move to 20–25 W/m and tighten toward 100–150 mm to reach the denser output a wet, high-loss room needs, with the IPX8, double-insulated and shielded build the page specifies. Keep runs clear of the drain and toilet fixings.
Cold retrofit over an existing floor. Height is limited and heat loss is high, so a 25 W/m cable at closer spacing delivers the density without a thick screed. Plan the cable length carefully because the usable area is often broken up by existing fittings.
Pipe frost protection. A lower 10–15 W/m cable, or the PTC variant, runs along the pipe under the insulation. The aim is to hold the pipe above freezing, not to heat a surface, so the logic is linear heat against pipe heat loss rather than area density.
Outdoor snow melting and ramps. The 30 W/m band at close spacing reaches the high area outputs needed to melt falling snow, controlled by slab temperature and moisture sensors. The same cable technology that heats a floor is run much denser outdoors because the load is far heavier.

Pre-order checklist
- The usable heated area, measured separately from the gross room size and excluding fixed fittings.
- The target area output in W/m² from the heat-loss calculation, noting whether the floor is primary or supplementary heat.
- The cable output in W/m and the planned spacing that together produce that density, checked against the table.
- The fixed cable length required, using length equals area times spacing, and confirmation that it covers the area without crossing runs.
- The minimum bend radius and minimum spacing for the chosen cable.
- The protection build: IPX8, double-insulated, shielded, on an RCD-protected circuit.
- The floor sensor position and the thermostat or contactor current rating at the project voltage.
Common selection mistakes
Treating W/m as the floor output. A 20 W/m cable is not a 20 W/m² floor; the spacing decides the real density. Always apply the division.
Planning to cut the cable to fit. A fixed-output cable cannot be shortened; size the length to the area before ordering.
Using the highest output everywhere. A 30 W/m cable at close spacing overheats an indoor floor. Match the band to the duty and reserve the top for outdoor work.
Letting spacing drift on site. Runs that bunch or touch create hot spots and warm stripes. Fix the spacing with a rail or clips before the screed.
Ignoring the sensor position. A sensor over a cable reads high and switches off early; place it in the gap for a true surface reading.
Data and evidence
The conversion between linear and area output is a geometric identity, not a marketing figure: dividing W/m by spacing in metres gives W/m², and the same geometry is used in every radiant-floor design method. Radiant floor standards such as EN 1264 set out pipe and cable spacing, floor surface limits and the use of control sensors, and they treat even spacing as the way to keep surface temperature variation small. Electrical insulation standards define the IPX8 rating and the double-insulated, shielded construction used for buried cables, and wiring rules require residual-current protection for elements embedded in the floor.
Heat-loss methods from building energy research calculate the area output needed to balance a room’s losses, which is why the design starts from the room rather than the cable catalogue. The squared relationship between surface temperature and radiant output also explains why over-dense floors overheat quickly and why a floor sensor is essential. On the factory side, SunAURA has produced resistive heating elements since 2008, runs ISO 9001 and 14001 systems with CE and RoHS documentation, and tests each cable circuit’s resistance and insulation before release; the product page carries a 15–25 year maintenance-free service window for correctly installed builds. No certificate number, customer name or external rating is invented, and the live product page should be treated as the source of confirmed figures.
Final recommendation
Work in this order. Calculate the target W/m² from the room’s heat loss. Pick a cable output band that fits the duty, low for pipe protection and comfort floors, 20–25 for indoor primary heat, 30 for outdoor melting. Then choose a spacing that converts that W/m into the target W/m² using the formula, and select the fixed cable length whose length covers the area at that spacing without touching or crossing. Hold the spacing even with a fixing rail, place the sensor in the gap, and protect the circuit with an RCD. Done that way, the floor delivers an even, controlled surface rather than warm stripes and cold edges, and the cable runs inside its rated temperature for its full service life.